133
133
23
Bypass Voltage Bad
Bypass voltage value is out of limit while UPS was operating on the bypass
mode.UPS will switch to normal mode if temperature and load status are
normal.If not ,UPS will stop.
24
Bypass Freq. Bad
Bypass frequency value is out of limit while UPS was operating on the bypass
mode.UPS will switch to normal mode if temperature and load status are
normal.If not ,UPS will stop.
25
Coil Overtemp
Over temperature is observed for UPS’ inverter and rectifier coils.
26
Inverter Voltage
Bad
Inverter voltage is out of limit. Load will be transferred to bypass line ,when
inverter voltage gets back to normal values,UPS will switch to normal mode
again.
27
Overload
Output load value is over %105, overloading counter will start to count , If UPS
is on normal mode , the charging will be stopped until load value gets back to
normal.
28
Maint. BYP. Sw. Off
Maintenance bypass switch is deactivated.
29
Ambient Nor.
Temp.
UPS ambient temperature has got back to allowed limit values.
30
Mains Voltage Nor.
Mains voltage is in the limited values , UPS will switch to normal mode.
31
Inverter Nor.
Temp.
Inverter temperature is in the limited values .If load and temperature values
are normal, UPS will switch to normal mode.
32
PFC Nor. Temp.
Rectifier temperature is in the limited values .If load and temperature values
are normal, UPS will switch to normal mode.
33
Charger Nor. Temp.
Charger/booster module temperature is in the allowed limits , charging will be
activated again.
34
STS Nor. Temp.
Temperature of Static transfer switches is in the allowed limit.
35
Bypass Voltage
Nor.
Bypass voltage is within defined limits.
36
Bypass Freq. Nor.
Bypass frequency is within defined limits.
37
Coil Normal temp.
UPS inverter or rectifier coil temperature has got back to normal values.
38
Inverter Volt.
Norm.
Inverter voltage is in the limited values , UPS will switch to normal mode.
39
Normal Load
Output load is under %100 , If charging was OFF , It will be ON .
40
BYP Thyr.L1 Short
C.
UPS has detected short circuit at bypass L1 thyristor.UPS will shut down.
41
BYP Thyr.L2 Short
C.
UPS has detected short circuit at bypass L2 thyristor.UPS will shut down.
42
BYP Thyr.L3 Short C
UPS has detected short circuit at bypass L3 thyristor.UPS will shut down.
43
UPS Thyr.L1 Short
C.
UPS has detected short circuit at inverter L1 thyristor.UPS will shut down.
44
UPS Thyr.L2 Short
C.
UPS has detected short circuit at inverter L2 thyristor.UPS will shut down.
45
UPS Thyr.L3 Short
C.
UPS has detected short circuit at inverter L3 thyristor.UPS will shut down.
46
UPS Thyr.L1 Open
C.
UPS has detected that inverter L1 thyristor can not be activated.Load will be
transferred to bypass line.
47
UPS Thyr.L2 Open
C.
UPS has detected that inverter L2 thyristor can not be activated.Load will be
transferred to bypass line.
Summary of Contents for IST5 Series
Page 2: ...2 2 SERVICE MANUAL 10 15 20 30 40 60 80 100 120 160 200 300 KVA...
Page 6: ...9 9 2 PRODUCT DESCRIPTION 2 1 General View 10 15 20 30 40KVA...
Page 7: ...10 10 60 80KVA...
Page 8: ...11 11 100 120 160 200 300 KVA...
Page 13: ...16 16 2 5 Side Interior View 10 15 20 30 40KVA...
Page 16: ...19 19 2 7 Electrical Connections...
Page 35: ...38 38...
Page 36: ...39 39...
Page 51: ...54 54 30 40KVA 60 80 100 120 160 200 300 KVA...
Page 54: ...57 57...
Page 71: ...74 74 1 Turn CB2 ON 10 15 20KVA 30 40KVA...
Page 72: ...75 75 60 80 100 120KVA 2 Stop the UPS using the user front panel Main menu Control Stop...
Page 73: ...76 76 3 Turn CB1 CB3 and CB4 OFF 10 15 20KVA 30 40KVA...
Page 100: ...103 103 Signal Flow Diagram zole trafo means isolated transformer...
Page 102: ...105 105 20 30KVA IGBT Driver 40KVA IGBT Driver...