2.11.4 Password-protected menus
Some menus such as the control menu are password
protected. Press to set each digit and press
ENTER to confirm.
2.11.5 Control Menu
Within the control menu, you can do one of the following:
Start
Start the UPS
Stop
Stop the UPS
Switch to BYPASS
Switch to static BYPASS mode
Switch to UPS
Switch to online mode
Bat. Quick Test
Start the quick battery test
Bat. Capacity Test
Start the deep battery test
Stop Battery Test
Stop the battery test
Battery status test, drains the 10% of battery
energy and reports batteries
which has more capacity than 10% as
“Good”
, less
capacity than 10% as
“Replace”
according to the test
results.
After UPS is started, it makes quick battery test every 24
hours and when test counter value is zero (0).
Note
: Batteries must be fully charged and kept floating for at least 1 hour before applying the
quick battery tests.
Batteries must be fully charged and kept in floating mode for at least 5 hours before performing
the battery tests.
Battery tests are performed by directing the power to the mains, independently from the loads.
If the mains values change during the test and are out of limits, the test will be canceled.
Status
> Battery
>menu timers shows the remaining time to the next test.
Summary of Contents for IST5 Series
Page 2: ...2 2 SERVICE MANUAL 10 15 20 30 40 60 80 100 120 160 200 300 KVA...
Page 6: ...9 9 2 PRODUCT DESCRIPTION 2 1 General View 10 15 20 30 40KVA...
Page 7: ...10 10 60 80KVA...
Page 8: ...11 11 100 120 160 200 300 KVA...
Page 13: ...16 16 2 5 Side Interior View 10 15 20 30 40KVA...
Page 16: ...19 19 2 7 Electrical Connections...
Page 35: ...38 38...
Page 36: ...39 39...
Page 51: ...54 54 30 40KVA 60 80 100 120 160 200 300 KVA...
Page 54: ...57 57...
Page 71: ...74 74 1 Turn CB2 ON 10 15 20KVA 30 40KVA...
Page 72: ...75 75 60 80 100 120KVA 2 Stop the UPS using the user front panel Main menu Control Stop...
Page 73: ...76 76 3 Turn CB1 CB3 and CB4 OFF 10 15 20KVA 30 40KVA...
Page 100: ...103 103 Signal Flow Diagram zole trafo means isolated transformer...
Page 102: ...105 105 20 30KVA IGBT Driver 40KVA IGBT Driver...