24
24
2.9.5
Maintenance Mode
On the maintenance mode loads are switched to the maintenance bypass line with a breaker, so
that the UPS can be serviced without cutting off the power to loads. The breaker is in full
conformity with capacity of loads.
2.10
Battery Management
Lead- acid batteries are used with UPSs.
2.10.1 Normal Operation Mode
Constant Charge Current
Constant current at 1/10 rate of the battery capacity is applied to battery, until reaches the float
voltage.
Float Charge
Depending on the battery discharge current the 1/3 of the battery energy is charged at this level.
With this level of charging batteries are kept ready for use at maximum capacity. For lead-acid
batteries, this voltage varies between values 2.2-2.35 V/cell. This voltage may differ slightly with
temperature adaptation. Option of setting this coefficient is provided with our UPS, we
recommend using the temperature sensor.
Summary of Contents for IST5 Series
Page 2: ...2 2 SERVICE MANUAL 10 15 20 30 40 60 80 100 120 160 200 300 KVA...
Page 6: ...9 9 2 PRODUCT DESCRIPTION 2 1 General View 10 15 20 30 40KVA...
Page 7: ...10 10 60 80KVA...
Page 8: ...11 11 100 120 160 200 300 KVA...
Page 13: ...16 16 2 5 Side Interior View 10 15 20 30 40KVA...
Page 16: ...19 19 2 7 Electrical Connections...
Page 35: ...38 38...
Page 36: ...39 39...
Page 51: ...54 54 30 40KVA 60 80 100 120 160 200 300 KVA...
Page 54: ...57 57...
Page 71: ...74 74 1 Turn CB2 ON 10 15 20KVA 30 40KVA...
Page 72: ...75 75 60 80 100 120KVA 2 Stop the UPS using the user front panel Main menu Control Stop...
Page 73: ...76 76 3 Turn CB1 CB3 and CB4 OFF 10 15 20KVA 30 40KVA...
Page 100: ...103 103 Signal Flow Diagram zole trafo means isolated transformer...
Page 102: ...105 105 20 30KVA IGBT Driver 40KVA IGBT Driver...