3.1.3.3 Internal Battery Configuration
The internal battery configuration is valid for the 10-15-20-30-40 kVA UPS only, it can be
configured by 62 paces 4,5 Ah, 7 Ah or 9Ah standard as following.
IST5 SERIS INTERNAL BATTERY USAGE TABLE
UPS POWER (KVA)
10KVA 15KVA 20KVA 30KVA 40KVA
BATTERIES IN SERIES
31
31
31
31
31
NUMBER OF PARALLEL ARMS
2
2
2
2
2
TOTAL NUMBER OF BATTERIES
62
62
62
62
62
I_bat_max @ V_bat_cut off. (A)
16,3
24,6
32,7
49,1
49,1
RECOMMENDED INTERNAL FUSE (A)
20
32
40
80
80
RECOMMENDED REAR PANEL FUSE (A)
20
32
40
80
80
*
Table shows recommended battery configurations.
*
Fast and semi-conductor protection type fuses are used for batteries.
The 7/9 Ah and 4.5 Ah batteries positioning can be seen at the following table;
Summary of Contents for IST5 Series
Page 2: ...2 2 SERVICE MANUAL 10 15 20 30 40 60 80 100 120 160 200 300 KVA...
Page 6: ...9 9 2 PRODUCT DESCRIPTION 2 1 General View 10 15 20 30 40KVA...
Page 7: ...10 10 60 80KVA...
Page 8: ...11 11 100 120 160 200 300 KVA...
Page 13: ...16 16 2 5 Side Interior View 10 15 20 30 40KVA...
Page 16: ...19 19 2 7 Electrical Connections...
Page 35: ...38 38...
Page 36: ...39 39...
Page 51: ...54 54 30 40KVA 60 80 100 120 160 200 300 KVA...
Page 54: ...57 57...
Page 71: ...74 74 1 Turn CB2 ON 10 15 20KVA 30 40KVA...
Page 72: ...75 75 60 80 100 120KVA 2 Stop the UPS using the user front panel Main menu Control Stop...
Page 73: ...76 76 3 Turn CB1 CB3 and CB4 OFF 10 15 20KVA 30 40KVA...
Page 100: ...103 103 Signal Flow Diagram zole trafo means isolated transformer...
Page 102: ...105 105 20 30KVA IGBT Driver 40KVA IGBT Driver...