134
134
48
UPS Thyr.L3 Open
C.
UPS has detected that inverter L3 thyristor can not be activated.Load will be
transferred to bypass line.
49
BYP Thyr.L1 Open
C.
UPS has detected that bypass L1 thyristor can not be activated.Load will be
transferred to inverter line.
50
BYP Thyr.L2 Open
C.
UPS has detected that bypass L2 thyristor can not be activated.Load will be
transferred to inverter line.
51
BYP Thyr.L3 Open
C.
UPS has detected that bypass L3 thyristor can not be activated.Load will be
transferred to inverter line.
52
Parl. Phs. Rot. Err.
One or more of UPSs which operate in paralel mode do not match in phase
sequence.
53
Battery Start
Starting through battery command has been given to UPS .
54
Parl. Start Error
One or more of UPSs which operate in paralel mode could not start to operate.
55
Inverter Fault
UPS couldn't prepare the inverter voltage.
56
Output Off
Static transfer switches all disabled. The loads can not be energized.
57
Normal Mode
UPS is operating in the normal mode,load are energized through rectifier –
inverter line.
58
Battery Mode
UPS is operating in the battery mode,load are energized through battery –
inverter line.
59
Bypass Mode
UPS is operating in the bypass mode,load are energized through bypass line.
60
Maint. Bypass
Mode
UPS is operating in the maintenance bypass mode,load are energized through
maintenance bypass line.
61
Parallel Mode
2 or more UPS are operating in power sharing mode. Load is fed through UPSs’
inverter lines.
62
Test Mode
UPS has switched to battery test mode,loads are energized through rectifier-
battery- inverter line as source sharing.
63
Manual Switch to
UPS
Switching to inverter(normal) mode command has been given via front panel.
64
Output Voltage
Error
Output voltage is detected during the period of starting UPS .UPS has been
stopped.
65
PFC Stop Cmd.
Abnormal stuation is detected during the moment of rectifier operating.UPS
has stopped itself.
66
Manuel Start
Command
Start command is given via UPS command menu.
67
Manuel Stop
Command
Stop command is given via UPS command menu.
68
UPS Stopped
UPS has been stopped.
69
Bypass Problem
UPS has switched to bypass mode so many times i a short period,UPS will be
shut down.
70
Parameters
Changed
Device-related parameters were changed on the service menu
71
Batterys Changed
Battery replacement date has been changed.battery statistics will be reset.
72
Load impact
Transfer
The load which can not be handled by inverter is activated. Loads will be
transferred to bypass line.
73
Parallel Command
UPS which is operating in paralel mode has been given a command to change
the status of static switches.
Summary of Contents for IST5 Series
Page 2: ...2 2 SERVICE MANUAL 10 15 20 30 40 60 80 100 120 160 200 300 KVA...
Page 6: ...9 9 2 PRODUCT DESCRIPTION 2 1 General View 10 15 20 30 40KVA...
Page 7: ...10 10 60 80KVA...
Page 8: ...11 11 100 120 160 200 300 KVA...
Page 13: ...16 16 2 5 Side Interior View 10 15 20 30 40KVA...
Page 16: ...19 19 2 7 Electrical Connections...
Page 35: ...38 38...
Page 36: ...39 39...
Page 51: ...54 54 30 40KVA 60 80 100 120 160 200 300 KVA...
Page 54: ...57 57...
Page 71: ...74 74 1 Turn CB2 ON 10 15 20KVA 30 40KVA...
Page 72: ...75 75 60 80 100 120KVA 2 Stop the UPS using the user front panel Main menu Control Stop...
Page 73: ...76 76 3 Turn CB1 CB3 and CB4 OFF 10 15 20KVA 30 40KVA...
Page 100: ...103 103 Signal Flow Diagram zole trafo means isolated transformer...
Page 102: ...105 105 20 30KVA IGBT Driver 40KVA IGBT Driver...