Chapter 5
System Hardware Configuration
5-3-5 Alarm Setting
To satisfy the needs of various applications,
ADAM-5000/TCP Series system provides Alarm setting function for
Analog Input and Counter Module. Users can set High/Low limit value
to identify the alarm status and trig- ger a digital output as an event
handling function.
Figure 5-16: Alarm Setting for Analog Input and Counter Modules
There are three alarm types in Analog Input Modules:
Disable:
ADAM-5000/TCP Series dose not executive alarm
diagnosing func- tion.
Momentary:
When the Input value is over or under the High/Low limit,
the alarm signal will be sent only once.
Latch:
When the input value is over or under the High/Low limit, the
alarm signal will be latched till clicking the “Clear Latch” button.
Note:
The alarm types of ADAM-5080 include “Disable” and “Latch
only.
5-14
ADAM-5000/TCP
User’s Manual