Planning Your Application Program
#aaSi
Name
Read All Channel Counter (Frequency) Data
Description
Return the input value of all channels for the speci-
fied input module for a specified system in engineer-
ing unit only.
Syntax #aaSi(cr)
#
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of the ADAM-5000/
TCP system you want to interrogate.
Si
is the I/O
slot of ADAM-5000 system you want to read.
(cr)
is the terminating character, carriage return (0Dh)
Response
>(data) (data) (data) (data) (cr)
if the command is valid.
?aa (cr)
if an invalid operation was entered. There
is no response if the module detects a syntax error
or communication error or if the specified ad- dress
does not exists.
> is a delimiter character.
?
is a delimiter character indicating the command
being invalid.
(data)
is the input value in engineering units of the
interrogated module of the specified system. If the
numbers of (data) are ten ,counter/frequency mode
is in decimal format. If the numbers of (data) are eight,
counter/frequency mode is in hexadecimal format. If
(data) = “ “, it means the channel is invalid.
(cr)
is the terminating character, carriage return (0Dh).
6-154
ADAM-5000/TCP
User’s Manual
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...