Chapter 6
Planning Your Application Program
$aaSiCjAhU(data)
Name
Set Alarm Limit
Description
Sets the High/Low alarm limit value for the specified
input channel of a specified ADAM-5000/TCP sys-
tem.
Syntax $aaSiCjAhU(data)(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.
SiCj
identifies the desired slot i (i : 0 to 7) and the
desired analog input channel j (j : 0 to 7).
AhU
is the
Set Alarm Limit command.
h
indicates alarm type and can have the value H =
High alarm, L = Low alarm
(data)
represents the desired alarm limit setting. The
format is always in engineering units.
(cr)
represents terminating character, carriage return
(0Dh)
Response !aa(cr)
if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
!
delimiter character indicating a valid command was
received.
aa
represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.
(cr)
represents terminating character, carriage return
(0Dh)
6-102
ADAM-5000/TCP
User’s Manual
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...