Planning Your Application Program
Chapter 6
$aaT
Name
Read I/O Type
Description
Returns the I/O module no. of all slots for a specified
ADAM-5000/TCP system.
Syntax $aaT(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal address of the ADAM-5000/TCP system
you want to interrogate.
T
is the I/O Module Types command.
(cr)
is the terminating character, carriage return (0Dh).
Response !aabbccddee(cr)
if the command is valid.
?aa(cr)
if an invalid operation was entered. There is
no response if the module detects a syntax error,
communication error or if the specified address does
not exist.
!
delimiter character indicating a valid command was
received.
?
delimiter character indicating the command was in-
valid.
aa
(range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.
bb, cc,
dd, ee
represent the I/O Module No. of all slots from
slot 0 thru 3 of the ADAM-5000/TCP system.
(cr)
is the terminating character, carriage return (0Dh).
Example
command:
$01T(cr)
response:
!0118245160(cr)
The command
requests the ADAM-5000/TCP sys- tem at address
01h to send all existing I/O module numbers. The
system at address 01h responds with I/O module
numbers 18, 24, 51 and 60 in slots 0-3. This means
that the ADAM-5000/TCP system contains an
ADAM-5018,ADAM-5024, ADAM-5051 and
ADAM-5060 in slots 0 thru 3.
ADAM-5000/TCP
User’s Manual
6-47
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...