Planning Your Application Program
#aaSi
Name
All Analog Data In
Chapter 6
Description
Returns the input value of all channels for a speci-
fied analog input module of a specified system in
engineering unit only.
Syntax #aaSi(cr)
#
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of the ADAM-5000/
TCP system you want to interrogate.
Si
is the I/O slot of ADAM-5000/TCP system you
want to read.
(cr)
is the terminating character, carriage return (0Dh)
Response
>(data) (data) (data) (data) (data) (data) (data) (data)
(cr)
if the command is valid.
?aa(cr)
if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exist.
> is a delimiter character indicating a valid command
was received.
?
delimiter character indicating the command was
invalid.
(data)
is the input value in engineering units of a
channel in the interrogated module of the specified
system. The (data) from all channels is shown in se-
quence from 7 to
0. If (data) = “ “, it means the channel is invalid.
(cr)
is the terminating character, carriage return (0Dh)
ADAM-5000/TCP
User’s Manual
6-69
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...