![Advantech ADAM-5000/TCP Series Manual Download Page 160](http://html1.mh-extra.com/html/advantech/adam-5000-tcp-series/adam-5000-tcp-series_manual_2857301160.webp)
Chapter 6
Planning Your Application Program
$aaSiCjAh
Name
Read Alarm Mode
Description
Returns the alarm mode for the specified channel in
the specified ADAM-5000/TCP system.
Syntax $aaSiCjAh(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.
SiCj
identifies the desired slot i (i : 0 to 7) and the
desired channel j (j : 0 to 7).
Ah
is the Read Alarm Mode command.
h
indicates alarm type and can have the value H =
High alarm, L = Low alarm
(cr)
represents terminating character, carriage return
(0Dh)
Response !aas(cr)
if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
!
delimiter character indicating a valid command was
received.
aa
represents the 2-character hexadecimal address
of the corresponding ADAM-5000/TCP system.
s
indicates alarm mode and can have the value M =
Momentary mode, L = Latching mode
(cr)
represents terminating character, carriage return
(0Dh)
6-92
ADAM-5000/TCP
User’s Manual
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...