Data Formats and I/O Ranges
Appendix B
Example 1
The input value is -2.65 V and the corresponding analog input module is
configured for a range of ±5 V. The response to the Analog Data
In command is:
-2.6500(cr)
Example 2
The input value is 305.5ºC. The analog input module is configured for a
Type J thermocouple whose range is 0ºC to 760ºC. The response to the
Analog Data In command is:
+305.50(cr)
Example 3
The input value is +5.653 V. The analog input module is configured for a
range of ±5 V range. When the engineering units format is used,
the ADAM Series analog input modules are configured so that they
auto- matically provide an over range capability. The response to the
Analog Data In command in this case is:
+5.6530(cr)
ADAM-5000/TCP
User’s Manual
B-3