![Advantech ADAM-5000/TCP Series Manual Download Page 248](http://html1.mh-extra.com/html/advantech/adam-5000-tcp-series/adam-5000-tcp-series_manual_2857301248.webp)
Planning Your Application Program
$aaSiCjAhCSkCn
Name
Set Alarm Connection
Chapter 6
Description
Connect the High/Low alarm of the specified input
channel to the specified digital output in
the ad- dressed ADAM-5000/TCP system
Syntax $aaSiCjAhCSkCn(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.
SiCj
identifies the desired slot i and the
desired chan- nel j .
AhC
is the command for setting Alarm Connection
command.
h
indicates alarm type and can have the value H =
High alarm, L = Low alarm
SkCn
identifies the desired slot k and the desired
digital output point n (n : 0 to F). To disconnect the
digital output, k and n should be set as ‘*’.
(cr)
represents terminating character, carriage return
(0Dh)
Response !aa(cr)
if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
!
delimiter character indicating a valid command was
received.
aa
represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.
ADAM-5000/TCP
User’s Manual
6-177
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...