Name
Read One Channel Counter (Frequency) Data
Description
The command will return the input value from one of
the four channels of a specified module.
Syntax #aaSiCj(cr)
#
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal Modbus address of the ADAM-5000/TCP sys-
tem you want to interrogate.
Si
identifies the I/O slot you want to interrogate.
Cj
identifies the channel you want to read.
(cr)
is the terminating character, carriage return (0Dh)
Response >(data)
if the command is valid.
?aa(cr)
if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exists.
> is a delimiter character.
?
delimiter character indicating the command was
invalid.
(data)
is the input value in engineering units of the
interrogated module of the specified system. If the
numbers of (data) are ten ,counter/frequency mode
is in decimal format. If the numbers of (data) are eight,
counter/frequency mode is in hexadecimal format. If
(data) = “ “, it means the channel is invalid.
(cr)
is the terminating character, carriage return (0Dh)
ADAM-5000/TCP
User’s Manual
6-157
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...