Planning Your Application Program
Chapter 6
@aaSiCjP(data)
Name
Set Initial Counter Value
Description
Set initial counter value for counter of the specified
counter module.
Syntax @aaSiCjP(data)(cr)
@
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal address of the ADAM-5000/TCP system.
SiCj
identifies the I/O slot i and the channel j for the
module you want to return a prior value.
P
represents
Set Initial Counter Value command.
(data)
is initial value from 0 to 4294967296. Be aware
that (data) has 10 characters.
(cr)
is the terminating character, carriage return (0Dh)
Response !aa(cr)
if the command is valid.
?aa(cr)
if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exist.
!
delimiter character indicating a valid command was
received.
?
delimiter character indicating the command was in-
valid.
aa
(range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.
(cr)
is the terminating character, carriage return (0Dh)
Example
command:
@01S3C2P0000004369(cr)
response:
!01(cr)
The channel 2 of ADAM-5080 in slot 3 in ADAM-
5000/TCP system at address 01h is instructed to set
initial counter value. The initial counter value is 4369.
ADAM-5000/TCP
User’s Manual
6-169
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...