3-5 Assigning address for I/O Modules
Basing on Modbus standard, the addresses of the I/O
modules you place into the ADAM-5000/TCP Series system are
defined by a simple rule. Please refer the figures 3-9 to map the I/O
address.
Figure 3-10: I/O Modules Address Mapping
For example,
if there is a ADAM-5024 (4-channel AO Module) in slot 2, the address of
this module should be 40017~40020.
Note:
ADAM-5080 is a special 4-channel counter module. The data
type is designed as “unsigned long”. When you
insert an ADAM-5080 in slot 0, the address should be 40001,
40003, 40005
and 40007.