Understanding Your System
Chapter 1
1-3-4 Power
•
Unregulated 10 to 30V
DC
•
Protection:
Over-voltage and power reversal
1-3-5 Isolation
•
Ethernet Communication:
1500 V
DC
•
I/O Module:
3000 V
DC
1-3-6 Mechanical
•
Case:
KJW with captive mounting hardware
•
Plug-in Screw Terminal Block:
Accepts 0.5 mm 2 to 2.5 mm 2 , 1 - #12 or 2 - #14 to #22 AWG
1-3-7 Environment
•
Operating Temperature:
- 10 to 70º C (14 to 158º F)
•
Storage Temperature:
- 25 to 85º C (-13 to 185º F)
•
Humidity:
5 to 95%, non-condensing
•
Atmosphere:
No corrosive gases
NOTE:
Equipment will operate below 30% humidity.
However, static electricity problems occur much more
frequently at lower hu- midity levels. Make sure you take
adequate precautions when you touch the equipment. Consider
using ground straps, anti- static floor coverings, etc. if you use
the equipment in low humidity environments.
1-3-8 Dimensions
The following diagrams show the dimensions
of the system unit and an I/O unit. All dimensions are in millimeters.
Figure 1-2: ADAM-5000/TCP system & I/O module dimensions
ADAM-5000/TCP
User’s Manual
1-7
355.0
331.5
309.5
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...