![Advantech ADAM-5000/TCP Series Manual Download Page 169](http://html1.mh-extra.com/html/advantech/adam-5000-tcp-series/adam-5000-tcp-series_manual_2857301169.webp)
Planning Your Application Program
Chapter 6
(cr)
represents terminating character, carriage return
(0Dh)
Example
command:
$01S0C1RLC(cr)
response:
!01S1C0(cr)
Channel 1 of slot 0 in the
ADAM-5000/TCP system at address 01h is
instructed to read its Low alarm output
connection. The system responds that the Low alarm
output con- nects to the digital output at point 0 of
slot 1 in the same ADAM-5000/TCP system.
ADAM-5000/TCP
User’s Manual
6-101