Planning Your Application Program
Response message format for function code 08:
Chapter 6
Command Body
StationAddress
FunctionCode
Data bytes received
Example:
01 08 00 02 00 04
Function Code 15 (0F hex)
Forces each coil in a
sequence of coils to either ON or OFF. Request message
format for function code 15:
Command Body
Requested Requested
Station Function
Start
Start
Numberof Numberof
Byte
Force
Force
Address
Code
Address Address
DataHigh DataLow
High Byte Low Byte Coil High
Byte
Coil Low
Byte
Count
Byte
Byte
Example:
Request to force a series of 10 coils starting at address 00020
(14 hex) in ADAM-5000/TCP.
01 0F 00 14 00 0A 02 CD 01
The query data contents are two bytes: CD 01 hex, equal to
1100 1101 0000 0001 binary. The binary bits are mapped to the
addresses in the following way.
Bit:1 1 0 0 1 1 0 1 0 0 0 0 0 0 0 1
Address (000XX): 27 26 25 24 23 2221 20 -------------------2928
Response message format for function code 15:
The normal responses return the station address, function code, start
address, and requested number of coil forced.
Command Body
Station
Address
Function
Code
Start
Address
High Byte
Start
Address
Low Byte
Requested
Numberof Coil
High Byte
Requested
Numberof Coil
Low Byte
Example:
01 0F 00 14 00 0A
ADAM-5000/TCP
User’s Manual
6-37
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...