![Advantech ADAM-5000/TCP Series Manual Download Page 250](http://html1.mh-extra.com/html/advantech/adam-5000-tcp-series/adam-5000-tcp-series_manual_2857301250.webp)
Planning Your Application Program
$aaSiCjRhC
Name
Read Alarm Connection
Chapter 6
Description
Return the High/Low alarm limit output connection
of a specified input channel in the addressed ADAM-
5000/TCP system
Syntax $aaSiCjRhC(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.
SiCj
identifies the desired slot i and the
desired chan- nel j.
RhC
is the command for reading
Alarm Connection.
h
indicates alarm type and can
have the value H = High alarm, L = Low alarm
(cr)
represents terminating character, carriage return
(0Dh)
Response !aaSkCn(cr)
if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
!
delimiter character indicating a valid command was
received.
aa
represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.
SkCn
identifies the desired slot k and the desired
digital output point n (n : 0 to F) to which the input
alarm is connected. If the values of k and n are ‘*’,
the analog input has no connection with a digital
output point.
ADAM-5000/TCP
User’s Manual
6-179
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...