Chapter 6
Planning Your Application Program
$aaSi0
Name
Read Digital filter scale
Description
Read the filter seconds to start to measure the input
signal.
Syntax $aaSi0(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal address of the ADAM-5000/TCP system which
is to be calibrate.
Si
identifies the I/O slot which is to be accessed.
0
is the command for reading digital filter scale.
(cr)
is the terminating character, carriage return (0Dh)
Response !aa(data)(cr)
if the command is valid.
?aa(cr)
if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exists.
!
delimiter character indicating a valid command was
received.
?
delimiter character indicating the command was in-
valid.
aa
(range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.
(data)
represents filter seconds from 8 µs~65000 µs.
Be aware that (data) has 5 characters.
(cr)
is the terminating character, carriage return (0Dh)
Example
command:
$01S30(cr)
response:
!0100765(cr)
The command requests the
ADAM-5080 in slot 3 of the ADAM-5000/TCP
system at address 01h to read the filter seconds. The
module responds with 765m seconds.
6-160
ADAM-5000/TCP
User’s Manual
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...