Planning Your Application Program
$aaSiCjAhU(data)
Name
Set Alarm Limit
Chapter 6
Description
Set the High/Low alarm limit value for the specified
input channel of a specified ADAM-5000/TCP sys-
tem.
Syntax $aaSiCjAhU(data)(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.
SiCj
identifies the desired slot i and the
desired chan- nel j.
AhU
is the Set Alarm Limit command.
h
indicates alarm type and can have the value H =
High alarm, L = Low alarm
(data)
represents the desired alarm limit setting. The
value is from 0 to 4294967295. Be aware that (data)
has 10 characters.
(cr)
represents terminating character, carriage return
(0Dh)
Response !aa(cr)
if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
!
delimiter character indicating a valid command was
received.
aa
represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.
ADAM-5000/TCP
User’s Manual
6-181
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...