Planning Your Application Program
$aaSiCjS
Name
Read Alarm Status
Chapter 6
Description
Read whether an alarm occurred for the specified
input channel in the specified ADAM-5000/TCP sys-
tem
Syntax $aaSiCjS(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.
SiCj
identifies the desired slot i and the
desired chan- nel j.
S
is the Read Alarm Status command.
(cr)
represents terminating character, carriage return
(0Dh)
Response !aahl(cr)
if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
!
delimiter character indicating a valid command was
received.
aa
represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.
h
represents the status of High alarm. ‘1’ means the
High alarm occurred, ‘0’ means it did not occur.
l
represents the status of Low alarm. ‘1’ means the
Low alarm occurred, ‘0’ means it did not occur.
(cr)
represents terminating character, carriage return
(0Dh)
ADAM-5000/TCP
User’s Manual
6-185
Summary of Contents for ADAM-5000/TCP Series
Page 1: ......
Page 23: ......
Page 44: ...4 I O modules...
Page 148: ......
Page 183: ......
Page 218: ......
Page 300: ...Appendix A Design Worksheets...
Page 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Page 308: ...Appendix B Data Formats and I O Ranges...
Page 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Page 324: ...Appendix C Grounding Reference...
Page 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...