Communication
72
Exception codes
The RETA-02 supports the Modbus exception codes shown
below.
Table 10.Supported exception codes
Function codes
The RETA-02 supports the Modbus function codes shown below.
Table 11.Supported function codes
Exception
code
Name
Description
01
Illegal
function
Unsupported command
02
Illegal data
address
Address does not exist or is read/write-
protected
03
Illegal data
value
Value is outside minimum and maximum
limits. Parameter is read-only
Function
code
Name
Description
Modbus
class
03
Read holding
registers
Reads the binary contents of the
holding registers (4X
references) in the slave.
0
06
Preset single
register
Presets a value into a single
holding register (4X reference).
1
16 (10h)
Preset
multiple
registers
Presets values into a sequence
of holding registers (4X
references).
0
23 (17h)
Read/Write
registers
Performs a combination of one
read and one write operation in
a single Modbus transaction.
The function first reads a group
of 4XXXX registers and then
writes new contents to a another
group of 4XXXX registers.
2
Summary of Contents for RETA-02
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 02 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 42: ...Drive configuration 42 ...
Page 48: ...Network configuration 48 ...
Page 50: ...Master configuration 50 ...
Page 58: ...Communication profiles 58 11 to 15 Drive specific Bit Name Value STATE Description ...
Page 68: ...Communication profiles 68 ...
Page 106: ...Diagnostics 106 ...
Page 111: ......