Quick start-up guide
25
Table 2. ACS800 parameter settings with PPO 6
Drive parameter
Example setting for ACS800
10.01 EXT1 STRT/STP/DIR
COMM.CW
10.03 REF DIRECTION
REQUEST
11.03 EXT1 REF1 SELECT
COMM.REF
16.04 FAULT RESET SEL
COMM.CW
98.02 COMM. MODULE LINK
FIELDBUS
98.07 COMM PROFILE
ABB DRIVES
51.01 MODULE TYPE
PROFINET IO
51.02 COMM RATE
0 (Auto-negotiation)
51.03 DHCP
0 (Disabled)
51.04 - 51.07 IP ADDRESS
10.0.0.6
51.08 - 51.11 SUBNET MASK
255.255.255.0
51.12 - 51.15 GW ADDRESS
0.0.0.0
51.16 PROTOCOL
1 (PROFINET IO)
51.18 OUTPUT 1
4001 (Gain for PID)
51.19 OUTPUT 2
2202 (Accel time 1)
51.20 OUTPUT 3
2203 (Decel time 1)
51.21 OUTPUT 4
3401 (Process variable)
51.22 INPUT 1
103 (Frequency)
51.23 INPUT 2
104 (Current)
51.24 INPUT 3
106 (Power)
51.24 INPUT 4
107 (DC bus voltage)
51.26 In/out 1-4 src
2 Disabled (Source of the
parameters selected on the PLC
side)