Quick start-up guide
28
changed through the configuration parameters unless
parameter 26 is set to 1 (Bus configuration parameters).
Table 3. ACS550 parameter settings with Std Telegram 1 + 4 PZD
Drive parameter
Example setting for ACS550
10.01 EXT1 COMMANDS
COMM
10.03 DIRECTION
REQUEST
11.03 REF1 SELECT
COMM
16.04 FAULT RESET SEL
COMM
98.02 COMM PROT SEL
EXT FBA
51.01 MODULE TYPE
PROFINET IO
51.02 COMM RATE
0 (Auto-negotiation)
51.03 DHCP
0 (Disabled)
51.04 - 51.07 IP ADDRESS
10.0.0.6
51.08 - 51.11 SUBNET MASK
255.255.255.0
51.12 - 51.15 GW ADDRESS
0.0.0.0
51.16 PROTOCOL
1 (PROFINET IO)
51.18 OUTPUT 1 (Read only)
4001 (Gain for PID)
51.19 OUTPUT 2 (Read only)
2202 (Accel time 1)
51.20 OUTPUT 3 (Read only)
2203 (Decel time 1)
51.21 OUTPUT 4 (Read only)
3401 (Process variable)
51.22 INPUT 1 (Read only)
103 (Frequency)
51.23 INPUT 2 (Read only)
104 (Current)
51.24 INPUT 3 (Read only)
106 (Power)
51.25 INPUT 4 (Read only)
107 (DC bus voltage)
51.26 In/out 1-4 src
2 Disabled (Source of the
parameters selected on the PLC
side)
Summary of Contents for RETA-02
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 02 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 42: ...Drive configuration 42 ...
Page 48: ...Network configuration 48 ...
Page 50: ...Master configuration 50 ...
Page 58: ...Communication profiles 58 11 to 15 Drive specific Bit Name Value STATE Description ...
Page 68: ...Communication profiles 68 ...
Page 106: ...Diagnostics 106 ...
Page 111: ......