Communication
82
unique identifiers for the connection, addressing information and
length of the record data. The response also contains two
additional fields for transferring information. See
Table 16.
for
details.
Table 16.Structure of the Read and Write blocks
Field(s)
Description
Range
Type
Service
Request or Response
service.
Request (0x00)
Response (0x80)
UI8
Operation
Read or Write operation.
Write (0x08)
Read (0x09)
UI8
Block
length
Length of the block.
0 … 0xFFFF
UI16
ARUUID
Identifier
- time low
- time mid
- time high and version
- clock
- node
UI32
UI16
UI16
Octet[2]
Octet[6]
API
Application Process
Identifier
Device Access Point
(0x0000)
PROFIdrive
(0x3A00)
UI32
Slot
Slot of the Module
Access Point (MAP/PAP)
0x01
UI16
Subslot
Subslot of the Module
Access Point (MAP/PAP)
0x01
UI16
Padding
2 bytes
Index
Index of the Record Data
Object
0x2F
0xB02E
0xB02F
UI16
Data length Length of the data block
0…0xFFFFFFFF
UI32
Summary of Contents for RETA-02
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 02 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 42: ...Drive configuration 42 ...
Page 48: ...Network configuration 48 ...
Page 50: ...Master configuration 50 ...
Page 58: ...Communication profiles 58 11 to 15 Drive specific Bit Name Value STATE Description ...
Page 68: ...Communication profiles 68 ...
Page 106: ...Diagnostics 106 ...
Page 111: ......