![background image](http://html.mh-extra.com/html/abb/reta-02/reta-02_user-manual_210095.webp)
Communication
95
947
V/P
R
Array [64]
Unsigned16
Fault number. (coded according to
DRIVECOM profile)
Subindex Contents
See parameter 945.
948
V/P
R
Array [n]
TimeDifference
Fault time
952
V/P
R/W Unsigned16
Number of faults occured. Writing a
zero clears the value.
953
V/P
R
Unsigned16
**Last alarm
954
V/P
R
Unsigned16
**Second last alarm
955
V/P
R
Unsigned16
**Third last alarm
956
V/P
R
Unsigned16
**Fourth last alarm
957
V/P
R
Unsigned16
**Fifth last alarm
964
V/P
R
Array [6]
Unsigned16
Device identification
Subindex Contents
0
Manufacturer
1
Device type
2
Version
3
Firmware date (year)
4
Firmware date
(day/month)
5
Number of Drive Objects
(DO)
965
P
R
Octet String2
Profile number of this device.
0329h = Profile 3, Version 41
967
V/P
R
Unsigned16
Control word (CW)
968
V/P
R
Unsigned16
Status word (SW)
Para-
meter
Mode
***
R/W
*
Data type
Description
Summary of Contents for RETA-02
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 02 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 42: ...Drive configuration 42 ...
Page 48: ...Network configuration 48 ...
Page 50: ...Master configuration 50 ...
Page 58: ...Communication profiles 58 11 to 15 Drive specific Bit Name Value STATE Description ...
Page 68: ...Communication profiles 68 ...
Page 106: ...Diagnostics 106 ...
Page 111: ......