Communication profiles
63
Table 7. The Control Word for the ABB Drives communication
profile. The upper case boldface text refers to the states shown in
Figure 11.
Bit
Name
Value
STATE/Description
0
OFF1_
CONTROL
1
Proceed to
READY TO OPERATE
.
0
Stop along currently active deceleration ramp.
Proceed to
OFF1 ACTIVE
; proceed to
READY TO
SWITCH ON
unless other interlocks (OFF2, OFF3)
are active.
1
OFF2_
CONTROL
1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to stop.
Proceed to
OFF2 ACTIVE
, proceed to
SWITCH-ON
INHIBITED
.
2
OFF3_
CONTROL
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined by drive
parameter. Proceed to
OFF3 ACTIVE
; proceed to
SWITCH-ON INHIBITED
.
Warning:
Ensure motor and driven machine can be
stopped using this stop mode.
3
INHIBIT_
OPERATION
1
Proceed to
OPERATION ENABLED
.
Note:
Run enable signal must be active; see drive
documentation. If the drive is set to receive the Run
enable signal from the fieldbus, this bit activates the
signal.
0
Inhibit operation. Proceed to
OPERATION
INHIBITED
.
4
RAMP_OUT_
ZERO
1
Normal operation. Proceed to
RAMP FUNCTION
GENERATOR: OUTPUT ENABLED
.
0
Force Ramp Function Generator output to zero.
Drive ramps to stop (current and DC voltage limits in
force).
Summary of Contents for RETA-02
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 02 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 42: ...Drive configuration 42 ...
Page 48: ...Network configuration 48 ...
Page 50: ...Master configuration 50 ...
Page 58: ...Communication profiles 58 11 to 15 Drive specific Bit Name Value STATE Description ...
Page 68: ...Communication profiles 68 ...
Page 106: ...Diagnostics 106 ...
Page 111: ......