Communication profiles
64
5
RAMP_HOLD
1
Enable ramp function.
Proceed to
RAMP FUNCTION GENERATOR:
ACCELERATOR ENABLED
.
0
Halt ramping (Ramp Function Generator output
held).
6
RAMP_IN_
ZERO
1
Normal operation. Proceed to
OPERATING
.
Note:
This bit is effective only if the fieldbus interface
is set as the source for this signal by drive
parameters.
0
Force Ramp Function Generator input to zero.
7
RESET
0=>1 Fault reset if an active fault exists. Proceed to
SWITCH-ON INHIBITED
.
Note:
This bit is effective only if the fieldbus interface
is set as the source for this signal by drive
parameters.
0
Continue normal operation.
8 to 9 Reserved.
10
REMOTE_
CMD
1
Fieldbus control enabled.
0
Control Word <> 0 or Reference <> 0: Retain last
Control Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus
control enabled. Reference and deceleration/
acceleration ramp are locked.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2. Effective if
control location parameterised to be selected from
fieldbus.
0
Select External Control Location EXT1. Effective if
control location parameterised to be selected from
fieldbus.
12 to
15
Reserved.
Bit
Name
Value
STATE/Description
Summary of Contents for RETA-02
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 02 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 42: ...Drive configuration 42 ...
Page 48: ...Network configuration 48 ...
Page 50: ...Master configuration 50 ...
Page 58: ...Communication profiles 58 11 to 15 Drive specific Bit Name Value STATE Description ...
Page 68: ...Communication profiles 68 ...
Page 106: ...Diagnostics 106 ...
Page 111: ......