Drive configuration
40
that are updated more frequently. Reading from the Modbus/TCP
register corresponding to the parameter is faster.
When PROFINET IO protocol is in use, these parameters define
the input (from drive to master) data words or drive parameters
that can be used with the vendor specific PPO’s or in addition to
the Standard telegram 1 (see chapter
Communication
). Input
words correspond to PZD's according to the table below.
*Inputs from 4 to 10 are defined separately in the PLC.
The contents are defined by a decimal number in the range of
0 to 65535 as follows:
Input
PZD
Input 1
PZD3
Input 2
PZD4
…
…
Input 8*
PZD10
0
Not used
1…99
Data set area of the drive
1
Data set 1 word 1
2
Data set 1 word 2
3
Data set 1 word 3
4
Data set 2 word 1
5
Data set 2 word 2
• • •
• • •
99
Data set 33 word 3
101…9999
Parameter area of the drive
Format: (x)xyy, where (x)x = actual
signal group or parameter group; yy
= actual signal or parameter index.
E.g. 103 = actual signal 01.03; 2202
= parameter 22.02.
10000…65535 Not supported by the drive
Summary of Contents for RETA-02
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 02 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 30: ...Mechanical installation 30 ...
Page 32: ...Electrical installation 32 ...
Page 42: ...Drive configuration 42 ...
Page 48: ...Network configuration 48 ...
Page 50: ...Master configuration 50 ...
Page 58: ...Communication profiles 58 11 to 15 Drive specific Bit Name Value STATE Description ...
Page 68: ...Communication profiles 68 ...
Page 106: ...Diagnostics 106 ...
Page 111: ......