4. For the maximum motor cable length with 4 kHz switching frequency, see section
Motor connection data (page 191)
WARNING!
The drive may cause radio interference if used in residential or
domestic environment. The user is required to take measures to prevent
interference, in association to the requirements for the CE compliance listed above,
if necessary.
Note:
Note: Do not install a drive with the EMC filter connected to a system that the
filter is not suitable for. This can cause danger, or damage the drive.
Note:
Do not install a drive with the ground-to-phase varistor connected to a system
that the varistor is not suitable for. If you do, the varistor circuit can be damaged.
If you install the drive to any other system than symmetrically grounded TN-S system,
you may need to disconnect the EMC filter or the ground-to-phase varistor. See section
Grounding system compatibility check (page 85)
.
■
Category C3
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter E200 or +E201.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. For the maximum motor cable length with 4 kHz switching frequency, see section
Motor connection data (page 191)
WARNING!
A drive of category C3 is not intended to be used on a low-voltage
public network which supplies domestic premises. Radio frequency interference
is expected if the drive is used on such a network.
Note:
Note: Do not install a drive with the EMC filter connected to a system that the
filter is not suitable for. This can cause danger, or damage the drive.
Note:
Do not install a drive with the ground-to-phase varistor connected to a system
that the varistor is not suitable for. If you do, the varistor circuit can be damaged.
If you install the drive to any other system than symmetrically grounded TN-S system,
you may need to disconnect the EMC filter or the ground-to-phase varistor. See section
Grounding system compatibility check (page 85)
.
■
Category C4
The drive complies with the C4 category with these provisions:
1. It is ensured that no excessive emission is propagated to neighboring low-voltage
networks. In some cases, the natural suppression in transformers and cables is
Technical data 197
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...