UL (NEC)3)
IEC1)
Frame
size
Drive type
ACS880-
11-…
Cu cable type
Al cable type 2)
Cu cable type
AWG/kcmil
mm2
mm2
4
3×35
3×25
R6
052A-5
3
3×50
3×35
R6
065A-5
2
3×70
3×35
R6
077A-5
1/0
3×70
3×50
R8
101A-5
3/0
3×95
3×95
R8
124A-5
4/0
3×150
3×120
R8
156A-5
300MCM
-
3×150
R8
180A-5
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three
ladder type trays one on top of the other, ambient temperature 30 °C, PVC insulation,
surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001). For other conditions,
size the cables according to local safety regulations, appropriate input voltage and the
load current of the drive.
2) Aluminum cables must not be used with drives of frame size R3.
3) The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-carrying
conductors in raceway or cable or earth (directly buried). For other conditions, size the
cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
4) In the USA, aluminum cables must not be used.
Temperature:
For IEC, select a cable rated for at least 70 °C maximum permissible
temperature of conductor in continuous use. For North America, power cables must be
rated for 75 °C (167 °F) or higher.
For surrounding air temperatures above 40 °C (104 °F) or frame R6 with B056
(UL Type 12), select a cable rated for at least 90 °C (194 °F) maximum permissible
temperature of conductor in continuous use.
Voltage:
600 V AC cable is accepted for up to 500 V AC.
Electrical power network specification
ACS880-11-xxxx-3 drives: 380…415 V AC 3-phase +10%…-15%. This
is indicated in the type designation label as typical input voltage level
3~400 V AC.
Voltage (
U
1)
ACS880-11-xxxx-5 drives: 380...500 V AC 3-phase +10%…-15%. This
is indicated in the type designation label as typical input voltage levels
3~400/480/500 V AC.
188 Technical data
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...