Use
1. Open the activation switch, or activate the safety functionality that is wired to the
STO connection.
2. The STO inputs on the drive control unit de-energize, and the control unit cuts off
the control voltage from the output IGBTs.
3. The control program generates an indication as defined by parameter
31.22
(see
the firmware manual of the drive).
4. The motor coasts to a stop (if running). The drive will not restart while the activation
switch or safety relay contacts are open.
5. Deactivate the STO by closing the activation switch, or resetting the safety
functionality that is wired to the STO connection.
6. Reset any faults before restarting.
WARNING!
The Safe torque off function does not disconnect the voltage of the main and
auxiliary circuits from the drive. Therefore maintenance work on electrical parts
of the drive or the motor can only be carried out after isolating the drive from the
supply and all other voltage sources.
WARNING!
The drive cannot detect or memorize any changes in the STO circuitry when the
drive control unit is not powered. If both STO circuits are closed and a level-type
start signal is active when the power is restored, it is possible that the drive starts
without a fresh start command. Take this into account in the risk assessment of
the system.
WARNING!
(With permanent magnet or synchronous reluctance [SynRM] motors only)
In case of a multiple IGBT power semiconductor failure, the drive can produce an
alignment torque which maximally rotates the motor shaft by 180/
p
degrees (with
permanent magnet motors) or 180/2
p
degrees (with synchronous reluctance
[SynRM] motors) regardless of the activation of the Safe torque off function.
p
denotes the number of pole pairs.
Notes:
• If a running drive is stopped by using the Safe torque off function, the drive will cut
off the motor supply voltage and the motor will coast to a stop. If this causes danger
or is not otherwise acceptable, stop the drive and machinery using the appropriate
stop mode before activating the Safe torque off function.
218 The Safe torque off function
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...