L1, L2, L3, T1/U, T2/V, T3/W, UD+, UDC- terminals
Cable entries
Frame
Tightening
torque
Max wire size
(solid/ stran-
ded)
Min wire size
(solid/ stran-
ded)
1)
Ø
pcs
N·m
mm2
mm2
mm
30
150
25
45
3
R8
1)
Note:
Only copper cables are allowed for drive types up to -039A-4.
For tightening torques of grounding terminals, see section
Screwdrivers for the terminals of the main circuit
Frame
Flat blade 0.6 x 3.5 mm
R3
L1, L2, L3, T1/U, T2/V, T3/W, UD+, UDC- terminals
Cable entries
Frame
Tightening
torque
Max wire size
(solid/ stran-
ded)
Min wire size
(solid/ stran-
ded)
Ø
pcs
lbf·ft
AWG
AWG
in
1.3
6
20
0.91
3
R3
4.1
2/0
10
1.77
3
R6
22.5
300
4
1.77
3
R8
For tightening torques of grounding terminals, see section
.
■
UL listed cable lugs and tools
Crimping tool
Compression lug
Wire size
kcmil/AWG
No. of crimps
Type
Manufacturer
Type
Manufacturer
1
TBM4S
Thomas &
Betts
E10731
54136
Thomas &
Betts
6
TBM45S
1
MY29-3
Burndy
YAV6C-L2
Burndy
2
ILC-10
Ilsco
CCL-6-38
Ilsco
1
TBM4S
Thomas &
Betts
54140
Thomas &
Betts
4
1
MY29-3
Burndy
YA4C-L4BOX
Burndy
1
MT-25
Ilsco
CCL-4-38
Ilsco
Technical data 185
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...