• Symbol # represents trip units. Trip units allowed include A thru C, E thru L, P
thru Z. If using Ekip breakers, set the overload current of the circuit breaker
equal to or less than the value shown in the “CB Maximum Current” column in
the tables below.
• The digits indicated with an “*” represent accessories for the breakers and have
no impact on the drive UL listing or performance or rating of the breaker.
6. Ratings in the tables are maximum for the given circuit breaker frame size. Breakers
with lower current ratings are also allowed if they have the same frame size,
interrupting rating, and voltage rating.
7. Using a circuit breaker with a lower kAIC rating is not allowed even if the available
short-circuit current is less than 65 kA.
8. When designing UL 508A panels, Article SB 4.2.3 Exception No. 3 allows the use
of other manufacturers' current limiting inverse time circuit breakers which have the
same voltage, current and interrupting rating, if
I
peak
and
I
2
t
are the same or less
than the ABB specified circuit breaker.
9. Only current limiting inverse time circuit breakers can be used.
10. The drives listed below have no Enclosure Minimum Volume unlike 480 V and 600 V
ACS880-01 drives.
Max.
Ipeak
Max. I2t
ABB circuit breaker
Drive
volume
CB
Voltage
CB
Maxim-
um
cur-
rent
Input
cur-
rent
Frame
ACS880-
11-…
kA
A2s
in3
V
A
A
U
n = 480 V
23.2
0.512×106
XT2Hαβ020#********
1638
480
20
5.8
R3
07A6-5
23.2
0.512×106
XT2Hαβ020#********
1638
480
20
7.8
R3
11A0-5
23.2
0.512×106
XT2Hαβ035#********
1638
480
35
10.6
R3
014A-5
23.2
0.512×106
XT2Hαβ035#********
1638
480
35
15.6
R3
021A-5
23.2
0.512×106
XT2Hαβ070#********
3507
480
70
21.3
R6
027A-5
23.2
0.512×106
XT2Hαβ070#********
3507
480
70
26.2
R6
034A-5
23.2
0.512×106
XT2Hαβ070#********
3507
480
70
31.2
R6
040A-5
23.2
0.512×106
XT2Hαβ125#********
3507
480
125
40.1
R6
052A-5
23.2
0.512×106
XT2Hαβ125#********
3507
480
125
49.5
R6
065A-5
23.2
0.512×106
XT2Hαβ125#********
3507
480
125
60.2
R6
077A-5
30
0.98×106
XT4Hαβ225#********
6602
480
225
74
R8
101A-5
30
0.98×106
XT4Hαβ225#********
6602
480
225
100
R8
124A-5
30
0.98×106
XT4Hαβ250#********
6602
480
250
120
R8
156A-5
30
0.98×106
XT4Hαβ250#********
6602
480
250
147
R8
180A-5
3AXD50000645015
178 Technical data
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...