Losses, cooling data and noise
The air flow direction is from bottom to top.
This table shows typical heat loss values, required air flow and noise at the nominal
ratings of the drive. The heat loss values can vary depending on voltage, cable conditions,
motor efficiency and power factor. To obtain more accurate values for given conditions,
use ABB DriveSize tool (
http://new.abb.com/drives/software-tools/drivesize
).
■
IEC
Frame
size
Noise
Air flow
Power losses
ACS880-11-…
dB(A)
ft3/min
m3/h
W
U
n = 400 V
R3
57
212
361
226
09A4-3
R3
57
212
361
329
12A6-3
R3
57
212
361
395
017A-3
R3
57
212
361
579
025A-3
R6
71
324
550
625
032A-3
R6
71
324
550
751
038A-3
R6
71
324
550
912
045A-3
R6
71
324
550
1088
061A-3
R6
71
324
550
1502
072A-3
R6
71
324
550
1904
087A-3
R8
68
537
913
1877
105A-3
R8
68
537
913
2963
145A-3
R8
68
537
913
3168
169A-3
R8
68
537
913
3990
206A-3
U
n = 500 V
R3
57
212
361
219
07A6-5
R3
57
212
361
278
11A0-5
R3
57
212
361
321
014A-5
R3
57
212
361
473
021A-5
R6
71
324
550
625
027A-5*
R6
71
324
550
711
034A-5*
R6
71
324
550
807
040A-5*
R6
71
324
550
960
052A-5*
R6
71
324
550
1223
065A-5*
R6
71
324
550
1560
077A-5*
R8
68
537
913
1995
101A-5
R8
68
537
913
2800
124A-5
R8
68
537
913
3168
156A-5
R8
68
537
913
3872
180A-5
182 Technical data
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...