• Make a 360° grounding of the power and control cable shields at the cable entries
to suppress electromagnetic disturbances.
• In a multiple-drive installation, connect each drive separately to the protective earth
(PE) busbar of the power supply.
Note:
• You can use power cable shields as grounding conductors only when their
conductivity is sufficient.
• As the normal touch current of the drive is higher than 3.5 mA AC or 10 mA DC, you
must use a fixed protective earth (PE) connection. The minimum size of the protective
earth conductor must comply with the local safety regulations for high protective
earth conductor current equipment. See standard IEC/EN 61800-5-1 and the electrical
planning instructions of the drive.
To comply with standard IEC/EN 61800-5-1:
• use a protective earth conductor with a minimum cross-sectional area of 10 mm
2
Cu or 16 mm
2
Al (as an alternative when aluminum cables are permitted),
or
• use a second protective earth conductor of the same cross-sectional area as the
original protective earth conductor,
or
• use a device that automatically disconnects the supply if the protective earth
conductor is damaged.
If the protective earth conductor is separate (that is, it does not form part of the input
power cable or the input power cable enclosure), the minimum cross-sectional area
must be:
• 2.5 mm
2
when the conductor is mechanically protected,
or
• 4 mm
2
when the conductor is not mechanically protected.
18 Safety instructions
3
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...