Nominal voltage of the drive
U
n
Continuous rms output current. No overload capability at 40 °C (104 °F)
I
n
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I
Ld
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
I
Hd
Note:
The ratings apply at an ambient temperature of 40 °C (104 °F).
High speed mode
Selection
High speed mode
of parameter
95.15 Special HW settings
improves control
performance at high output frequencies. ABB recommends it to be selected with output
frequency of 120 Hz and above.
This table gives the drive ratings for the maximum output frequency when
High speed
mode
in parameter
95.15 Special HW settings
is enabled: With output frequencies
smaller than this recommended maximum output frequency, the current derating is less
than the values given in the table. Contact ABB for operation above the recommended
maximum output frequency or for the output current derating with output frequencies
above 120 Hz and below the maximum output frequency.
At the output frequency 120 Hz no derating.
Output ratings with selection High speed mode of parameter 95.15 Spe-
cial HW settings
ACS880-11-
Heavy-duty use
Light-duty use
Nominal use
Maximum output
frequency
IHd
ILd
IN
fmax
A
A
A
Hz
U
n = 400 V
6.5
8.1
8.5
500
09A4-3
8.5
10.7
11.3
500
12A6-3
11.3
14.3
15
500
017A-3
15.0
20.9
22
500
025A-3
22
29
30
500
032A-3
30
33
35
500
038A-3
35
39
41
500
045A-3
41
53
56
500
061A-3
47
53
56
500
072A-3
56
64
67
500
087A-3
87
100
105
500
105A-3
105
138
145
500
145A-3
122
148
156
500
169A-3
155
180
192
500
206A-3
U
n = 500 V
Technical data 169
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...