Using a safety switch between the drive and the motor
ABB recommends to install a safety switch between the permanent magnet motor and
the drive output. The switch is needed to isolate the motor from the drive during
maintenance work on the drive.
Implementing an ATEX-certified motor thermal protection
With Q971, the drive provides ATEX-certified safe motor disconnection without
contactor using the drive Safe torque off function. To implement the thermal protection
of a motor in explosive atmosphere (Ex motor), you must also:
• use an ATEX-certified Ex motor
• order an ATEX-certified thermistor protection module for the drive (L537),
or acquire and install an ATEX-compliant protection relay
• do the necessary connections.
For more information, see:
Manual code
(English)
User's manual
ATEX-certified Safe disconnection function, Ex II (2) GD for ACS880 drives
(+Q971) application guide
FPTC-02 ATEX-certified thermistor protection module, Ex II (2) GD (option
+L537+Q971) for ACS880 drives user's manual
Controlling a contactor between drive and motor
The control of the output contactor depends on how you use the drive, that is, which
motor control mode and which motor stop mode you select.
If you have the DTC motor control mode and the motor ramp stop mode selected, use
this operation sequence to open the contactor:
1. Give a stop command to the drive.
2. Wait until the drive decelerates the motor to zero speed.
3. Open the contactor.
If you have the DTC motor control mode and the motor coast stop, or scalar control
mode selected, open the contactor as follows:
1. Give a stop command to the drive.
2. Open the contactor.
Guidelines for planning the electrical installation 79
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...