Note:
Fuses from other manufacturers can be used if they meet the ratings and the
melting curve of the fuse does not exceed the melting curve of the fuse mentioned in
the table.
■
aR fuses DIN 43653 stud-mount
Ultrarapid (aR) fuses (stud-mount, one fuse per phase)
Input cur-
rent
Min.
short-cir-
cuit cur-
rent1)
ACS880-
11-…
Type DIN
43653
Buss-
mann type
Voltage
rating
I2t
Nominal
current
V
A2s
A
A
A
3-phase
U
n = 400 V
000
170M1311
690
130
25
8
70
09A4-3
000
170M1311
690
130
25
10
70
12A6-3
000
170M1311
690
130
25
14
70
017A-3
000
170M1312
690
270
32
20
100
025A-3
000
170M1313
690
460
40
27
110
032A-3
000
170M1315
690
1450
63
33
210
038A-3
000
170M1316
690
2550
80
40
300
045A-3
000
170M1316
690
2550
80
51
300
061A-3
000
170M1317
690
4650
100
63
400
072A-3
000
170M1318
690
8500
125
76
400
087A-3
000
170M1319
690
16000
160
88
700
105A-3
000
170M1320
690
28000
200
120
970
145A-3
00
170M2618
690
42000
250
144
1100
169A-3
00
170M2619
690
68500
315
176
1600
206A-3
3-phase
U
n = 500 V
000
170M1308
690
25.5
10
5.8
32
07A6-5
000
170M1309
690
48
16
7.8
42
11A0-5
000
170M1311
690
130
25
10.6
65
014A-5
000
170M1311
690
130
25
15.6
65
021A-5
000
170M1313
690
460
40
21.3
120
027A-5
000
170M1315
690
1450
63
26.2
170
034A-5
000
170M1315
690
1450
63
31.2
170
040A-5
000
170M1316
690
2550
80
40.1
280
052A-5
000
170M1317
690
4650
100
49.5
400
065A-5
000
170M1318
690
8500
125
60.2
400
077A-5
000
170M1319
690
16000
160
71
700
101A-5
000
170M1320
690
28000
200
96
970
124A-5
00
170M2618
690
42000
250
115
1100
156A-5
00
170M2619
690
68500
315
141
1600
180A-5
Technical data 171
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...