R3: Do not disconnect EMC or VAR screws.
PE
L3
L2
L1
R6: Disconnect EMC DC screw. Do not disconnect EMC
AC or VAR screws.See Note 1 below.
R8: Disconnect EMC DC and VAR screws.
IT systems (ungrounded or high-resistance grounded [>30 ohms])
R3: Disconnect EMC and VAR screws.
L3
L2
L1
R6: Disconnect EMC AC, EMC DC and VAR screws.
R8: Disconnect EMC DC and VAR screws.
TT systems
R3: Disconnect EMC and VAR screws.
N
L3
L2
L1
R6: Disconnect EMC AC, EMC DC and VAR screws.
R8: Disconnect EMC DC and VAR screws.
Residual current device has to be installed in the supply
system.
Note:
• Because the EMC filter screws have been disconnec-
ted, ABB does not guarantee the EMC category.
• ABB does not guarantee the functioning of the ground
leakage detector built inside the drive.
• In large systems the residual current device can trip
without a real reason.
Note 1:
Frames R3 and R6 are evaluated for use on corner-grounded systems and
midpoint-grounded delta systems by UL standards. They are not evaluated by IEC
standards for use on corner-grounded or midpoint-grounded systems.
Note 2:
These are the EMC filter and varistor screws of different drive frame sizes.
Ground-to-phase varistor screws
EMC filter (oE200 and +E202)
screws
Frame size
VAR
EMC
R3
VAR
EMC AC, EMC DC
R6
Electrical installation – IEC 87
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...