Output ratings with selection High speed mode of parameter 95.15 Spe-
cial HW settings
ACS880-11-
Heavy-duty use
Light-duty use
Nominal use
Maximum output
frequency
IHd
ILd
IN
fmax
A
A
A
Hz
4.4
6.2
6.5
500
07A6-5
6.5
8.9
9.4
500
11A0-5
9.4
11.4
12.0
500
014A-5
12.0
17.1
18.0
500
021A-5
18.0
21.9
23.0
500
027A-5
23
28
29
500
034A-5
23
28
29
500
040A-5
29
35
37
500
052A-5
33
37
39
500
065A-5
39
44
46
500
077A-5
77
91
101
500
101A-5
96
118
124
500
124A-5
87
136
144
500
156A-5
147
160
169
500
180A-5
Nominal voltage of the drive
U
n
Maximum output frequency with High speed mode
f
max
Continuous rms output current. No overload capability at 40 °C (104 °F).
I
n
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I
Ld
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
I
Hd
Derating for output voltage boost
See
ACS880-11, ACS880-31, ACS880-14, ACS880-34, ACS880-17, ACS880-37 drives
product note on DC voltage boost
(
[English]).
Fuses (IEC)
Fuses protect the input cable in short-circuit situations. They also restrict drive damage
and prevent damage to adjoining equipment in case of a short-circuit inside the drive.
ABB recommends the high speed aR fuses specified below. The gG fuses can be used
for frames R3 and R6 if they operate rapidly enough (max. 0.1 seconds). The operating
time depends on the supply network impedance and the cross-sectional area and length
of the supply cable. Obey the local regulations.
170 Technical data
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...