![background image](http://html.mh-extra.com/html/abb/acs880-11/acs880-11_hardware-manual_2643137.webp)
Connector pitch 5 mm, wire size 2.5 mm2
Analog inputs AI1 and AI2
(XAI:4 … XAI:7).
Current input: –20…20 mA,
R
in = 100 ohm
Current/voltage input mode selec-
tion by jumpers
Voltage input: –10…10 V,
R
in > 200 kohm
Differential inputs, common mode range ±30 V
Sampling interval per channel: 0.25 ms
Hardware filtering: 0.25 ms, adjustable digital filtering up to
8 ms
Resolution: 11 bit + sign bit
Inaccuracy: 1% of full scale range
Connector pitch 5 mm, wire size 2.5 mm2
Analog outputs AO1 and AO2
(XAO)
0…20 mA,
R
load < 500 ohm
Frequency range: 0…300 Hz
Resolution: 11 bit + sign bit
Inaccuracy: 2% of full scale range
Connector pitch 5 mm, wire size 2.5 mm2
XD2D connector
Physical layer: RS-485
Transmission rate: 8 Mbit/s
Cable type: Shielded twisted-pair cable with a twisted pair
for data and a wire or another pair for signal ground (nom-
inal impedance 100 … 165 ohm, for example Belden 9842)
Maximum length of link: 50 m (164 ft)
Termination by jumper
Connector pitch 5 mm, wire size 2.5 mm2
Safe torque off connection (XSTO)
Input voltage range: -3…30 V DC
Logic levels: "0" < 5 V, "1" > 17 V.
Note:
For the unit to start, both connections must be “1”.
This applies to all control units (including drive, inverter,
supply, brake, DC/DC converter etc. control units), but true
Safe torque off functionality is only achieved through the
XSTO connector of the drive/inverter control unit.
EMC (immunity) according to IEC 61326-3-1
Connector: RJ-45
Control panel connection (X13)
Cable length < 3 m
The terminals of the control unit fulfill the Protective Extra Low Voltage (PELV) requirements.
The PELV requirements of a relay output are not fulfilled if a voltage higher than 48 V is connected
to the relay output.
Control units of the drive 137
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...