European Union and United Kingdom
To meet the European Union Directives and United Kingdom Regulations, according
to standard EN 60204-1,
Safety of Machinery
, the disconnecting device must be one
of the following types:
• switch-disconnector of utilization category AC-23B (IEC 60947-3)
• disconnector that has an auxiliary contact that in all cases causes switching devices
to break the load circuit before the opening of the main contacts of the disconnector
(EN 60947-3)
• circuit-breaker suitable for isolation in accordance with IEC 60947-2.
North America
Installations must be compliant with NFPA 70 (NEC)
1)
and/or Canadian Electrical Code
(CE) along with state and local codes for your location and application.
1)
National Fire Protection Association 70 (National Electric Code).
Other regions
The disconnecting device must conform to the applicable local safety regulations.
■
DC solar PV main power supply
When you perform maintenance or wiring activities in the drive cabinet, make sure that:
• you disconnect Solar PV supply at string combiner box level
or
• remove the solar PV connections before installing the drive cabinet
or
• remove DC fuse inside drive cabinet.
Selecting the main contactor
You can equip the drive with a main contactor.
Follow these guidelines when you select a customer-defined main contactor:
• Dimension the contactor according to the nominal voltage and current of the drive.
Also consider the environmental conditions such as surrounding air temperature.
• IEC devices only: Select contactor with utilization category AC-1 (number of
operations under load) according to IEC 60947-4,
Low-voltage switch gear and
control gear.
• Consider the application life time requirements.
54 Guidelines for planning the electrical installation
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...