UL (NEC) RATINGS
Output ratings
Max.
current
Input
current
Frame
size
ACS880-11-
Heavy-duty use
Light-duty use
App.
power
PHd
IHd
PLd
ILd
Sn
Imax
I1
hp
A
hp
A
kVA
A
A
10.0
14.0
15.0
21.0
18
26.3
15.6
R3
021A-5
15.0
21.0
20.0
27.0
23
35.7
21.3
R6
027A-5
1)
20.0
27.0
25.0
34.0
29
45.9
26.2
R6
034A-5
1)
25.0
34.0
30.0
40.0
35
57.8
31.2
R6
040A-5
1)
30.0
40.0
40.0
52.0
45
68.0
40.1
R6
052A-5
40.0
52.0
50.0
65.0
56
88.4
49.5
R6
065A-5
1)
50.0
65.0
60.0
77.0
67
110.5
60.2
R6
077A-5
1)
60.0
77.0
75.0
96.0
87
148
74
R8
101A-5
75.0
96.0
100.0
124.0
107
178
100
R8
124A-5
100.0
124.0
125.0
156.0
137
247
120
R8
156A-5
125.0
156.0
150.0
180.0
156
287
147
R8
180A-5
3AXD00000588487
1) These ratings are not to be used for drives with degree of protection of IP55 (UL Type 12) B056.
Nominal voltage of the drive
U
n
Nominal input current (rms) at 40 °C (104 °F)
I
1
Maximum output current. Available for 10 seconds at start, otherwise as long as allowed
by drive temperature. 140% … 200% of
I
Hd, depending on power rating.
I
max
Continuous rms output current. No overload capability at 40 °C (104 °F). This is indicated
in the type designation label as output current
I
2.
I
2
Typical motor power in no-overload use
P
n
Apparent power (no overload)
Sn
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I
Ld
Typical motor power for light-overload use
P
Ld
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
I
Hd
Typical motor power for heavy-duty use
P
Hd
Note:
To achieve the rated motor power given in the table, the rated current of the drive must be
higher than or equal to the rated motor current. The power ratings apply to most IEC 34 motors
at the nominal voltage of the drive.
ABB recommends to select the drive, motor and gear combination for the required motion profile
with the DriveSize dimensioning tool available from ABB.
Technical data 163
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...