Motor connection data
Asynchronous AC induction motors, permanent magnet synchronous
motors in open loop control, AC induction servomotors, synchronous re-
luctance motors
Motor types
The drive provides solid state short circuit protection for the motor con-
nection per IEC/EN 61800-5-1 and UL 61800-5-1.
Short-circuit current
protection
(IEC/EN/UL 61800-5-1)
0.…500 Hz
Frequency (
f
2)
For drives with du/dt filter: 120 Hz
For drives with sine filter: 120 Hz
0.01 Hz
Frequency resolution
See section
.
Current
2 kHz, 4 kHz, 8 kHz, 12 kHz, (depends on the frame and parameter set-
tings)
Switching frequency
For frame R3: 150 m (492 ft)
Maximum recommen-
ded motor cable length For frames R6 and R8: 300 m (984 ft).
Note 1
: With motor cables longer than 150 m (492 ft) or switching fre-
quencies higher than default, the EMC Directive requirements may not
be fulfilled.
Note 2
: Longer motor cables cause a motor voltage decrease which
limits the available motor power. The decrease depends on the motor
cable length and characteristics. Contact ABB for more information. Note
that a sine filter (optional) at the drive output also causes a voltage de-
crease.
Control unit (ZCU-12) control unit connection data
See
.
Efficiency
Efficiency at nominal power level:
Approximately 96% for frame R3
Approximately 96.5% for frame R6
Approximately 97% for frame R8
Energy efficiency (ecodesign)
Energy efficiency data is not provided for the drive. The regenerative drives are exempt
from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c) and the UK
ecodesign requirements (Regulation SI 2021 No. 745).
Technical data 191
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...