220 Parameters
Broadcast
The control word and reference 1 are sent by the master to all
followers. If the master has this setting, the parameter has no
effect in the followers.
0
Ref1 MC Grps
The drive-to-drive control word and reference 1 are only sent
to the drives in the multicast group specified by parameter
. This setting can also used in
intermediate followers to form a multicast chain.
1
57.12
Ref1 mc group
Selects the multicast group the drive belongs to. See
parameter
0…62
Multicast group.
1 = 1
57.13
Next ref1 mc grp
Specifies the next multicast group of drives the multicast
message is relayed to. See parameter
This parameter is effective only in the master or intermediate
followers (i.e. followers relaying the message to other
followers).
0
No group selected.
0
1…62
Next multicast group in the chain.
1 = 1
57.14
Nr ref1 mc grps
In the master drive, sets the total number of links (followers or
groups of followers) in the multicast message chain. See
parameter
Notes:
• This parameter has no effect if the drive is a follower.
• The master counts as a member of the chain if
acknowledgement from the last drive to the master is
desired.
1…62
Number of links in the multicast chain.
1 = 1
57.15
D2D com port
Defines the hardware to which the drive-to-drive link is
connected. In special cases (such as harsh operating
conditions), the galvanic isolation provided by the RS-485
interface of the FSCA module may make for more robust
communication than the standard drive-to-drive connection.
on-board
Connector X5 on the JCU Control Unit is used.
0
Slot 1
An FSCA module installed in JCU option slot 1 is used.
1
Slot 2
An FSCA module installed in JCU option slot 2 is used.
2
Slot 3
An FSCA module installed in JCU option slot 3 is used.
3
64
64 Load analyzer
Peak value and amplitude logger settings. See also section
on page
64.01
PVL signal
Selects the signal to be monitored by the peak value logger.
The signal is filtered using the filtering time specified by
parameter
.
The peak value is stored, along with other pre-selected
signals at the time, into parameters
.
Parameter
resets both the peak value
logger and amplitude logger 2. The latest time the loggers
were reset is stored into parameter
.
Speed rpm
(see page
1073742081
Speed %
(see page
1073742082
Frequency
(see page
1073742083
Current
(see page
).
1073742084
Current %
(see page
).
1073742085
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...