280 Fieldbus control
After the module configuration parameters have been set, the drive control
parameters (see section
below) must be checked and
adjusted when necessary.
The new settings will take effect when the drive is powered up the next time (before
powering off the drive, wait at least 1 minute), or when parameter
is activated.
–
Displays the fieldbus adapter module
mapping file revision stored in the memory
of the drive.
–
Displays the status of the fieldbus adapter
module communication.
–
Displays the common program revision of
the adapter module.
–
Displays the application program revision of
the adapter module.
Note:
In the
User’s Manual
of the fieldbus adapter module, the parameter group number is 1
TRANSMITTED DATA SELECTION (see also page
…
4…6
14…16
101…9999
Defines the data transmitted from drive to
fieldbus controller.
Note:
If the selected data is 32 bits long,
two parameters are reserved for the
transmission.
…
1…3
11…13
1001…9999
Defines the data transmitted from fieldbus
controller to drive.
Note:
If the selected data is 32 bits long,
two parameters are reserved for the
transmission.
Note:
In the
User’s Manual
of the fieldbus adapter module, the parameter group number is 3
or C for parameters
.
Parameter
Setting for
fieldbus control
Function/Information
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...