![ABB ACS850-04 series Firmware Manual Download Page 113](http://html1.mh-extra.com/html/abb/acs850-04-series/acs850-04-series_firmware-manual_3365228113.webp)
Parameters 113
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
DIO6
Digital input/output DIO6 (as indicated by
,
bit 5).
1074070019
Const
Bit pointer setting (see
on page
). -
Pointer
10.10
Fault reset sel
Selects the source of the external fault reset signal. The
signal resets the drive after a fault trip if the cause of the fault
no longer exists.
0 -> 1 = Fault reset.
Note:
A fault reset from the fieldbus is always observed
regardless of this setting.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
DIO6
Digital input/output DIO6 (as indicated by
,
bit 5).
1074070019
Const
Bit pointer setting (see
on page
). -
Pointer
10.11
Run enable
Selects the source of the external run enable signal. If the run
enable signal is switched off, the drive will not start, or coasts
to stop if running.
1 = Run enable.
Note:
This parameter cannot be changed while the drive is
running.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
DIO6
Digital input/output DIO6 (as indicated by
,
bit 5).
1074070019
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...